Final | 5/23/2019 | 5/24/2019 | 5/24/2019 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Renea Rich - final ok occ card not onsite to sign
|
Final | 5/7/2019 | 5/8/2019 | 5/7/2019 | P | CANC |
Jack Reynolds
|
|
|
Phone #: ###-#### >> Inspection requested via web by Renea Rich Inspection cancelled from web by: Renea Rich
|
Rough-in | 2/19/2019 | 2/20/2019 | 2/20/2019 | A | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Kaila Martarano - R/I ok - exhaust fans ok
|
Rough-in | 2/6/2019 | 2/6/2019 | 2/6/2019 | P | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Kaila Martarano - still need to see exhaust fan specs - line sets and condensate lines need nail plates - exhaust ducting needs sealed at fan outlets - west unit first floor was locked wasnt able to inspect
|
Rough-in | 1/25/2019 | 1/28/2019 | 1/28/2019 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Kaila Martarano - need to see install instructions for 1hr rated exhaust fans - exhaust ducts need sealed - condensate lines need to be an approved material and a min 3/4" in size
|