Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMEC19-00382
StatusFinaled
Name DIAMOND HEATING AND COOLING
Site Address 4522 N BUCKBOARD PL
Project Name 
Customer Number16427226
ePlanReviewNo
Description
Alteration or Repair: REPLACEMENT OF EXISTING FURNACE AND AC COIL WITH 96% FURNACE AND 16 SEER AC COIL
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/8/20192/8/20192/8/2019PPASS
DetailsBrian Scoles
made corrections and sent photos of bubble wrap that is now double wrapped to have proper insulation. Please call me if any issues, my name is Steve Dale Phone #: ###-#### Inspection requested via web by Rick Montgomery
Final1/30/20191/31/20191/31/2019AFAIL
DetailsBrian Scoles
PLEASE CALL STERLING WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace a/c coil co ok- bubble wrap insulation needs 3/4" air gap per installation instructions to maintain R-6 value whats installed on meets R-4.2- talked with steve about this by phone