Permit Information
Permit NumberMEC19-01051
StatusFinaled
Name INTEGRITY HEATING & AIR LLC
Site Address 10600 W CRUSER DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: Install new complete HVAC in new construction residential home with gas piping.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/28/20195/28/20195/28/2019APASS
DetailsBrian Scoles
meet at 1130- duct blast witnes and final- duct blast test pass- final ok
Final5/23/20195/24/20195/24/2019AFAIL
DetailsBrian Scoles
lift up garage door it is unlocked Phone #: ###-#### Inspection requested via web by Terek Worley- water heater flue not addressed in correction- still no duct blast done- need to schedule duct if your doing test or 3rd party
Final5/15/20195/15/20195/15/2019PFAIL
DetailsBrian Scoles
garage code 1234 Phone #: ###-#### Inspection requested via web by Terek Worley- need duct blast test completed and if done by integrity will need to be witneesed- water heater flue needs to be ran in all single wall or b vent can not go from b vent at china cap to single wall back to b vent
Rough-in3/25/20193/25/20193/25/2019PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Terek Worley- R/I ok
Rough-in3/21/20193/22/20193/22/2019AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Terek Worley- need city approved and stamped manual J onsite- outside air can not tie into R/A can needs tied into plenum- contractor needs to provide ladder to access furnace and coil in attic- left notice front window
Pressure Test3/21/20193/22/20193/22/2019APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Terek Worley- 20lb gas pass- tagged meter location