Permit Information
Permit NumberMEC19-01095
StatusExpired
Name DIAMOND HEATING AND COOLING
Site Address 5205 W CASSIA ST
Project NameEickmeier Remodel
Customer Number16610534
ePlanReviewNo
Description
Alteration or Repair: replacement of existing furnace and ac coil with 96% furnace and 14 seer ac coil. Replacing all new duct work and Man J is sent and approved and stamped copy onsite.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Mec-Aging Inspection4/15/20204/15/20204/15/2020 PASS
DetailsJack Reynolds
Doc Permit Expired ok
DOC - Permit Expired4/15/20204/15/20204/15/2020APASS
DetailsJack Reynolds
Doc Permit Expired ok permit not active
Mec-Aging Inspection1/15/20201/15/20201/15/2020 DONE
DetailsJack Reynolds
Talked with Steve from Diamond Heating about their mechanical aging permit. Contractor has attemped to contract homeowner with no success. Permit will expire at next mechanical aging inspection if not active.
Mec-Aging Inspection10/16/201910/16/201910/16/2019 DONE
DetailsJack Reynolds
WIP
Final7/17/20197/18/20197/18/2019PFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Adam Eickmeier
- need to see 5lb flue pressure test on water heater flue that was moved
- also will need to see installation instructions for water heater
Rough-in3/21/20193/22/20193/22/2019APASS
DetailsJack Reynolds
Johnny Phone #: ###-####
- R/I ok
- will need to see a 5lb flue test on existing water heater flue that was moved by final
Rough-in3/20/20193/21/20193/21/2019ANR
DetailsJack Reynolds
PLEASE CALL OUR LEAD INSTALLER SAM WHEN 30-45 MINS IN ROUTE SO WE HAVE HAVE FLUE UNDER PRESSURE FOR YOU WHEN YOU ARRIVE. CORRECTIONS TO MAN J MADE AND APPROVED BY TROY JAMES AND THAT COPY OF MAN J HAS BEEN REPLACED AND LOCATED ONSITE FOR YOU. Phone #: ###-#### Inspection requested via web by Rick Montgomery
- tried calling Sam and left a voicemail. showed up onsite and no access
Rough-in3/18/20193/19/20193/19/2019PFAIL
DetailsChad Schwendiman
PLEASE CALL OUR LEAD INSTALLER SAM WHEN IN ROUTE. CLIENT IS WANTING TO MOVE TO NEXT STAGE WITH SHEETROCK AND WE ARE READY FOR ROUGH INSPECTION PLEASE. Phone #: ###-#### Inspection requested via web by Rick Montgomery -
1) Need to pressure test pvc flue
2) Equipment installed doesn't match the approved manual J
3) Missing 8" supply in kitchen
4) Supply branch lines feeding the main level are not sized per the approved manual J. Manual J shows 8" they were ran in 7"