Permit Information
Permit NumberMEC19-01134
StatusFinaled
Name ICON AIR
Site Address 11434 W GREYLING CT
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: Installing HVAC and Fireplace
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/16/20195/17/20195/17/2019APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
Final5/15/20195/16/20195/16/2019AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Randy Hart- need air balance report onsite
Rough-in3/29/20194/1/20194/1/2019PPASS
DetailsBrian Scoles
re inspection Phone #: ###-#### Inspection requested via web by Randy Hart- R/I ok- need to secure flue in attic by final no supports
Pressure Test3/29/20194/1/20194/1/2019PPASS
DetailsBrian Scoles
re inspection Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass- tagged meter location
Rough-in3/28/20193/29/20193/29/2019AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Randy Hart-
1- fireplace instructions on inside of glass need to be readily accessible
2- all supply and R/A registers need to be sealed with mastic
3- need ladder provided by contractor to access furnace/coil in attic
4- all exhaust fan connections need sealed where metal duct ties on to plastic fan housing under flex
5- ducting pinched off in attic above master bath needs to flow smoothly on 2 supply runs
6- need nail plate flor and ceiling both sides of framing on condensate drain 2nd floor and ceiling 1st floor
7- range ducting needs tape sealed to pipe has gaps
8- gas test fail at 14psi
9- b vent in garage between joists needs 1" clearance

left correction notice front living room window on inside
Pressure Test3/28/20193/29/20193/29/2019AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Randy Hart- gauge at 14psi