Permit Information
Permit NumberMEC19-01266
StatusFinaled
Name ALL PRO LLC
Site Address 2513 N 31ST ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: new HVAC for duplex
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/9/20199/10/20199/10/2019PPASS
DetailsBen Livingston
Phone #: ###-#### Inspection requested via web by David Shartzer
Rough-in6/3/20196/4/20196/4/2019PPASS
DetailsBen Livingston
Phone #: ###-#### Inspection requested via web by David Shartzer
Rough-in5/29/20195/30/20195/30/2019AFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by David Shartzer
- condensate lines on the mini split system needs to be a min 3/4" and approved material
- all line sets need support in the attic
- need to see range venting for r/i on north side. South side range needs one more joint sealed at the top of vent
- line set on south side is sticking out of the wall
- need access to air handler in attic
Rough-in5/25/20195/28/20195/29/2019PNH
DetailsBen Livingston
Phone #: ###-#### Inspection requested via web by David Shartzer
no access