Pressure Test | 5/23/2019 | 5/24/2019 | 5/24/2019 | A | CANC |
Jack Reynolds
|
|
|
Please call with any questions, access to work area through alley behind house. Phone #: ###-#### Inspection requested via web by Joey Hickman
|
Final | 5/20/2019 | 5/23/2019 | 5/23/2019 | P | PASS |
Jack Reynolds
|
|
|
Please call Joey before hand ###-####. Phone #: ###-#### Inspection requested via web by Joey Hickman - furnace ac coil co ok
|
Final | 5/7/2019 | 5/8/2019 | 5/8/2019 | P | FAIL |
Jack Reynolds
|
|
|
Call Joey @ ###-#### prior to arrival Final inspection for furnace change out. Phone #: ###-#### Inspection requested via web by Joey Hickman - gas line at furnace needs a sediment trap installed after shut off - door into mech room needs to be weather stripped and self closing - A/C power whip needs to be weather tight conduit and line set needs some arma flex insulation installed with UV protection
|