Final | 5/6/2019 | 5/7/2019 | 5/7/2019 | A | PASS |
Jack Reynolds
|
|
|
Inspection requested via web by Kelli Morgan - final ok
|
Pressure Test | 5/6/2019 | 5/7/2019 | 5/7/2019 | A | PASS |
Jack Reynolds
|
|
|
Inspection requested via web by Kelli Morgan - 20lb gas pressure test ok
|
Final | 5/6/2019 | 5/6/2019 | 5/6/2019 | P | FAIL |
Jack Reynolds
|
|
|
Inspection requested via web by Kelli Morgan -20lb gas pressure test fail gauge was under 20lb
|
Final | 5/1/2019 | 5/6/2019 | 5/6/2019 | A | CANC |
Jack Reynolds
|
|
|
AM INSPECTION PLEASE. PLEASE CALL ###-#### WHEN ON WAY Phone #: ###-#### Inspection requested via web by Kelli Morgan - pressure test fail
|
Pressure Test | 5/1/2019 | 5/6/2019 | 5/6/2019 | A | FAIL |
Jack Reynolds
|
|
|
AM INSPECTION PLEASE. PLEASE CALL ###-#### WHEN ON WAY Phone #: ###-#### Inspection requested via web by Kelli Morgan - gauge being used needs to be a 30lb gauge at 20lb - when performing a section test either disconnect new gas line from live gas line or install a tell tale (shut off valve to open ended tee to another shut off valve)
|