Mec-Aging Inspection | 7/28/2020 | 7/28/2020 | 7/28/2020 | | FAIL |
Jack Reynolds
|
|
|
Permit has not been active since 1-31-20. Schedule inspection if work is finished. Pictures of corrections will be ok. Permit will expire at next mechanical aging inspection if not active.
|
Mec-Aging Inspection | 4/28/2020 | 4/28/2020 | 4/28/2020 | | FAIL |
Jack Reynolds
|
|
|
Schedule inspection with owner if corrections have been made. Permit was active last on 1-31-20.
|
Final | 1/28/2020 | 1/31/2020 | 1/31/2020 | A | FAIL |
Jack Reynolds
|
|
|
Call when on the way to ensure home owner is home. Phone #: ###-#### Inspection requested via web by Dan McFate - co ok -wet switch and primary too close to furnace vent. Change out single wall for b vent to achieve clearances. threaded pvc fittings for condensate need sealed so they wont leak
|
Mec-Aging Inspection | 12/17/2019 | 12/17/2019 | 12/17/2019 | | FAIL |
Jack Reynolds
|
|
|
Need to re schedule inspection once corrections have been made. This permit has not been active since failing on 9-18-19
|
Final | 9/17/2019 | 9/18/2019 | 9/18/2019 | A | FAIL |
Jack Reynolds
|
|
|
Please call when you are on the way so we can make sure someone is home or we can meet you there Phone #: ###-#### Inspection requested via web by Dan McFate - need to see co sensors installed near bedrooms - primary drain on indoor coil needs repaired and glued - secondary drain needs a wet switch installed - pump tubing installed is too close to single wall furnace flue. Keep in mind clearances to combustibles on furnace flue
|