Permit Information
Permit NumberMEC19-01922
StatusIssued
Name MCFATE HEATING SERVICE
Site Address 420 S SIERRA DR
Project Name 
Customer Number12383
ePlanReviewNo
Description
Alteration or Repair: Install AC
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Mec-Aging Inspection7/28/20207/28/20207/28/2020 FAIL
DetailsJack Reynolds
Permit has not been active since 1-31-20. Schedule inspection if work is finished. Pictures of corrections will be ok. Permit will expire at next mechanical aging inspection if not active.
Mec-Aging Inspection4/28/20204/28/20204/28/2020 FAIL
DetailsJack Reynolds
Schedule inspection with owner if corrections have been made. Permit was active last on
1-31-20.
Final1/28/20201/31/20201/31/2020AFAIL
DetailsJack Reynolds
Call when on the way to ensure home owner is home. Phone #: ###-#### Inspection requested via web by Dan McFate
- co ok
-wet switch and primary too close to furnace vent. Change out single wall for b vent to achieve clearances. threaded pvc fittings for condensate need sealed so they wont leak
Mec-Aging Inspection12/17/201912/17/201912/17/2019 FAIL
DetailsJack Reynolds
Need to re schedule inspection once corrections have been made. This permit has not been active since failing on 9-18-19
Final9/17/20199/18/20199/18/2019AFAIL
DetailsJack Reynolds
Please call when you are on the way so we can make sure someone is home or we can meet you there Phone #: ###-#### Inspection requested via web by Dan McFate
- need to see co sensors installed near bedrooms
- primary drain on indoor coil needs repaired and glued
- secondary drain needs a wet switch installed
- pump tubing installed is too close to single wall furnace flue. Keep in mind clearances to combustibles on furnace flue