Final | 7/3/2019 | 7/3/2019 | 7/3/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Sorensen- final ok
|
Final | 7/1/2019 | 7/2/2019 | 7/2/2019 | A | PART |
Brian Scoles
|
|
|
Final - call Brandon Phone #: ###-#### Inspection requested via web by Brandon Sorensen- need air balance report- need to seal north unit on top and side of transition and reinstall screws missing on units- need hangers installed on south unit- unistrut feet need attached to supports on north unit- recall in when ready
|
Rough-in | 6/27/2019 | 6/28/2019 | 6/28/2019 | A | PASS |
Brian Scoles
|
|
|
Rough in Phone #: ###-#### Inspection requested via web by Brandon Sorensen- R/I ok- need to pull electrical permit for 2 new disconnects outside and get inspected- need airbalance at final
|
Conference | 6/25/2019 | 6/26/2019 | 6/26/2019 | A | DONE |
Brian Scoles
|
|
|
courtesy inspection - call brandon Phone #: ###-#### Inspection requested via web by Brandon Sorensen- walked job with Brandon- need to be code compliant on ducts ran outside need to be insulated to R-12 per 2015 IECC- call in R/I i nspection when ready
|