Permit Information
Permit NumberMEC19-02063
StatusFinaled
Name ACTION HEATING & COOLING
Site Address 7002 W PETRIE ST
Project NameBrowning Addition
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Install new gas furnace and duct work //8-29-19 TCH Added exit fans and exhaust fan
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/18/201910/18/201910/18/2019PPASS
DetailsBrian Scoles
Brad Phone #: ###-####- final ok
Rough-in8/29/20198/29/20198/29/2019APART
DetailsBrian Scoles
Met with bld inspector onsite- ok to cover- soon as man j approved recall in R/I inspection-
Rough-in8/28/20198/28/20198/28/2019PPART
DetailsBrian Scoles
OK to cover pending man j- will need another R/I inspection completed as soon as man j approved and onsite
Rough-in8/22/20198/23/20198/23/2019PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Brad Knapton-
1- need to submit man j to city for approval and have approved man j onsite for inspection
2- crawl needs completedon R/I and air balance will need to be done on new ducting at final
3- need to add 1 exhaust fan and duct work to permit and pay fee
4- no gas test found

left notice
Pressure Test5/20/20195/21/20195/21/2019APASS
DetailsBrian Scoles
2#meter Phone #: ###-#### Inspection requested via web by Brad Knapton- 60lb gas pass- tagged meter location
Pressure Test5/20/20195/20/20195/20/2019PFAIL
DetailsBrian Scoles
Pressure test only Phone #: ###-#### Inspection requested via web by Brad Knapton- gauge wont zero out stuck around 40psi