Final | 9/9/2019 | 9/9/2019 | 9/9/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- both units ok
|
Final | 9/5/2019 | 9/6/2019 | 9/6/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- south and noth unit needs continous fan operational- need to add arma flex at condenser couple places bare copper seen- need to seal the both chasse weather/rodent proof tight- missing register 1st floor both units- need approved man j onsite- all equipment needs to be operational
|
Final | 8/30/2019 | 8/30/2019 | 8/30/2019 | P | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP
|
Final | 8/20/2019 | 8/20/2019 | 8/20/2019 | P | NR |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- condensers havent been set- all penetrations will need sealed
|
Rough-in | 5/31/2019 | 5/31/2019 | 5/31/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- R/I both units ok
|
Rough-in | 5/29/2019 | 5/30/2019 | 5/30/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- need approved man j onsite for both units- both units floor and atticg need fireblocking installed on exhaust fan ducting in closets and framing completed where flex duct penetrates floor and attic in approved method and fire caulked
|
Rough-in | 5/23/2019 | 5/23/2019 | 5/23/2019 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- wrong address- need to get permit issued for right unit
|