Permit Information
Permit NumberMEC19-02181
StatusFinaled
Name TML LLC
Site Address 2121 N COLE RD
Project Name 
Customer Number23118-13
ePlanReviewNo
Description
New: New HVAC, Split Systems, ductwork GRD''S, misc.
Includes test & balance, DDC Controls.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/23/20198/23/20198/23/2019APASS
DetailsBrian Scoles
Jake is your contact Phone #: ###-#### Inspection requested via web by Kim Adams- final ok- card signed
Final8/15/20198/16/20198/16/2019APART
DetailsBrian Scoles
Jake is your contact Phone #: ###-#### Inspection requested via web by Kim Adams- Temp occupancy ok- All roof penetrations need roofed in- Is air balance done ?
Final8/14/20198/15/20198/15/2019APART
DetailsBrian Scoles
Jake is your contact Phone #: ###-#### Inspection requested via web by Kim Adams- need to label f/s dampers on grid- need to roof in all penetrations on roof- secondary drains from coil can not tie into primary furnace drains- air balance still needs completed- temp occupamcy ok this permit only- other mech contractor inspection still needs on gas piping called in
Rough-in8/5/20198/7/20198/7/2019APART
DetailsBrian Scoles
Robert is the contact Phone #: ###-#### Inspection requested via web by stan lillquist- R/I ok on 4 classrooms and hallway ok for ceiling tiles-
Rough-in7/11/20197/12/20197/12/2019APASS
DetailsBrian Scoles
bathrooms and offices, Robert is your contact. Phone #: ###-#### Inspection requested via web by stan lillquist- 2 fire/smoke damper framong and clearances ok, ok for angles- seal on ducts in classrooms, offices and bathrooms ok- ok to cover- still need to look at linesets for a/cs and minisplits- ok for ceiling grid
Rough-in6/18/20196/19/20196/19/2019APASS
DetailsChad Schwendiman
Duct sealing inspection. Robert is the contact Phone #: ###-#### Inspection requested via web by stan lillquist