Final | 8/21/2019 | 8/22/2019 | 8/22/2019 | A | PASS |
Chad Schwendiman
|
|
|
Final inspection. Please contact Lou at ###-#### prior to arrival on-site. Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Card not on site to sign | 8/22/2019 | 8/22/2019 | 8/22/2019 | A | PASS |
Chad Schwendiman
|
|
|
Final inspection. Please contact Lou at ###-#### prior to arrival on-site. Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 7/30/2019 | 7/31/2019 | 7/31/2019 | A | FAIL |
Chad Schwendiman
|
|
|
Cover inspection. Please contact Lou prior to arrival on--site at ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Need duct mounted smoke detectors, Flex duct to long, approved plans state flex duct limited to 3'. Need to complete straping for liner diffusers, need to seal adjustable elbow on supply duct
|