Final | 7/17/2019 | 7/17/2019 | 7/17/2019 | P | PASS |
Jack Reynolds
|
|
|
Antonio is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist - final ok no occ card to sign
|
Card not on site to sign | 7/17/2019 | 7/17/2019 | 7/17/2019 | P | PASS |
Jack Reynolds
|
|
|
Antonio is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist - Occ card not onsite to sign
|
Final | 6/26/2019 | 6/27/2019 | 6/27/2019 | A | FAIL |
Jack Reynolds
|
|
|
Antonio is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist - economizer needs installed on RTU and plumbing vent needs to be 3' above economizer - rtu needs condensate ptrap installed - need to see t shirt dryer installation manual to check venting requirements - will want to see dryers installed for final
|
Rough-in | 6/19/2019 | 6/20/2019 | 6/20/2019 | P | FAIL |
Jack Reynolds
|
|
|
Antonio is the contact Phone #: ###-#### Inspection requested via web by stan lillquist - few areas need duct sealed finished above ceiling - duct work above ceiling will need insulated after being sealed - venting for dryer system needs installed and I will need manufactures installation instructions onsite at time of inspection
|
Final | 6/19/2019 | 6/20/2019 | 6/20/2019 | P | NR |
Jack Reynolds
|
|
|
Antonio is the contact Phone #: ###-#### Inspection requested via web by stan lillquist
|