Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMEC19-02466
StatusFinaled
Name TML LLC
Site Address 7106 W MCMULLEN ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Install 2 AC 2 Furnace
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/20/20198/23/20198/23/2019APASS
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Denise Colin
Final7/3/20197/5/20197/5/2019AFAIL
DetailsChad Schwendiman
OUR TECHS WILL BE ON SITE BY 9:30 Phone #: ###-#### Inspection requested via web by Marisa Hone - Need to complete UV protection on line set, Need 6" clearance between pvc pipe and single wall water heater flue, Can not draw cmbustion air from a bathroom.
Pressure Test7/3/20197/5/20197/5/2019APASS
DetailsChad Schwendiman
OUR TECHS WILL BE ON SITE BY 9:30 Phone #: ###-#### Inspection requested via web by Marisa Hone - 5lb flue pass
Pressure Test6/26/20196/28/20196/27/2019ACANC
DetailsBrian Scoles
Pressure test & final 10:30 >> Inspection requested via web by Marisa Hone Inspection cancelled from web by: Marisa Hone
Final6/26/20196/28/20196/27/2019ACANC
DetailsBrian Scoles
Pressure test & final 10:30 >> Inspection requested via web by Marisa Hone Inspection cancelled from web by: Marisa Hone
Final6/19/20196/26/20196/26/2019ACANC
DetailsBrian Scoles
Pressure test & Final 1030-11am >> Inspection requested via web by Marisa Hone Inspection cancelled from web by: Marisa Hone
Pressure Test6/19/20196/26/20196/26/2019ACANC
DetailsBrian Scoles
Pressure test & Final 1030-11am >> Inspection requested via web by Marisa Hone Inspection cancelled from web by: Marisa Hone
Final6/13/20196/18/20196/18/2019ACANC
DetailsBrian Scoles
pressure test scheduled 10:30-11am >> Inspection requested via web by Marisa Hone Inspection cancelled from web by: Marisa Hone
Pressure Test6/13/20196/18/20196/18/2019ACANC
DetailsBrian Scoles