Final | 11/13/2019 | 11/14/2019 | 11/14/2019 | A | PASS |
Brian Scoles
|
|
|
Francisco is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist- final ok- card signed
|
Rough-in | 8/29/2019 | 8/29/2019 | 8/29/2019 | P | PASS |
Brian Scoles
|
|
|
cover exhaust duct, Francisco is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist- exhaust fan seal ok- flex, registers and insulation all areas ok- ok to cover- need roof access at final
|
Rough-in | 8/28/2019 | 8/28/2019 | 8/28/2019 | P | PART |
Brian Scoles
|
|
|
Francisco is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist- column 4 thru 8 insulation and registers ok- ok for sheetrock this area only- seal on duct column 2 thru 4 supply and r/a ok- ok to insulate- still need to look at exhaust ducting
|
Rough-in | 8/21/2019 | 8/21/2019 | 8/21/2019 | A | PART |
Brian Scoles
|
|
|
Rough In for duct approval to insulate. Francisco is your contact ###-#### Phone #: ###-#### Inspection requested via web by Kim Adams- seal on all duct for RTU at grid line 6 ok- ok to insulate- linear diffusers ok - still need to see exhaust fan and ducting installed
|
Rough-in | 8/13/2019 | 8/15/2019 | 8/15/2019 | A | PART |
Brian Scoles
|
|
|
Francisco is the contact Phone #: ###-#### Inspection requested via web by stan lillquist- Rtu at grid line 3 ducting and seal ok ok to insulate- rtu bewteen grid 4 and 5 ducting and seal ok ok to insulate- studio area seal on duct ok ok to insulate- recall in when other rtu ducting is completed- went over with Francisco onsite
|