Permit Information
Permit NumberMEC19-02558
StatusFinaled
Name S & K PLUMBING SERVICES LLC
Site Address 421 S CURTIS RD Unit: 113
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: NEW HOME
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/7/20204/8/20204/8/2020PPASS
DetailsBrian Scoles
GARAGE CODE: 4343 Phone #: ###-#### Inspection requested via web by Kristy Watson- final ok
Mec-Aging Inspection4/7/20204/7/20204/7/2020 FAIL
DetailsBrian Scoles
texted contractor to check in on this aging permit
Final1/7/20201/8/20201/8/2020AFAIL
DetailsBrian Scoles
GARAGE CODE: 4343 Phone #: ###-#### Inspection requested via web by Kristy Watson- need locking caps on service ports on a/c- need uv protection on lineset at a/c- need to remove stucco around gas pipe and seal- need air balance report onsite- duct blast test needs completed
Mec-Aging Inspection1/7/20201/7/20201/7/2020 FAIL
DetailsBrian Scoles
needs called in for final inspection-WIP
Rough-in6/26/20196/26/20196/26/2019PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Kristy Watson- R/I ok
Rough-in6/19/20196/19/20196/19/2019PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Kristy Watson- corrections not all made- supply duct in crawl still needs 4" clearance off ground at crawl hole location
Rough-in6/17/20196/17/20196/17/2019PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Kristy Watson
1- duct in crawl needs minimum 4" clearance off ground
2- b vent at roof needs 1" clearance to combustibles laying against plywood sheathing
3- need to seal all spot welds on supply and return boots
4- need to seal dryer duct to termination box in wall
5- need to resubmit man J to city for approval and have approved man j onsite with equipment brand installed- shows payne and has bryant installed

left correction notice front window
Pressure Test6/17/20196/17/20196/17/2019PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Kristy Watson- 20lb gas pass tagged meter location