Final | 8/22/2019 | 8/22/2019 | 8/22/2019 | P | PASS |
Jack Reynolds
|
|
|
Please do a flue pressure test and final inspection. Call Jesse at ###-#### 1/2 hour before so he can meet you there, thanks. Inspection requested via web by 4 Seasons - final ok
|
Pressure Test | 8/22/2019 | 8/22/2019 | 8/22/2019 | P | CANC |
Jack Reynolds
|
|
|
Please call Jesse one half hour before so he can meet you there at ###-####, thanks. >> Inspection requested via web by 4 Seasons Inspection cancelled from web by: 4 Seasons
|
Rough-in | 7/24/2019 | 7/25/2019 | 7/25/2019 | A | PASS |
Jack Reynolds
|
|
|
Please call James at ###-#### with any questions, thanks. Inspection requested via web by 4 Seasons - R/I ok - flue test failed again re test
|
Pressure Test | 7/25/2019 | 7/25/2019 | 7/25/2019 | A | FAIL |
Jack Reynolds
|
|
|
Please call James at ###-#### with any questions, thanks. Inspection requested via web by 4 Seasons - 5lb flue pressure test fail gauge was under 5lb
|
Rough-in | 7/22/2019 | 7/23/2019 | 7/23/2019 | A | FAIL |
Jack Reynolds
|
|
|
Please call James at ###-#### one half hour before so someone can meet you there to let you in, thanks. Inspection requested via web by 4 Seasons - single wall water flue needs clearances to PVC flue for furnace - 5lb flue pressure test fail - need access doors to damper motors - dryer length is too long -duct work in new stair case needs sealed - bedroom in basement needs return air/ transfer installed
|
Pressure Test | 7/23/2019 | 7/23/2019 | 7/23/2019 | A | FAIL |
Jack Reynolds
|
|
|
Please call James at ###-#### one half hour before so someone can meet you there to let you in, thanks. Inspection requested via web by 4 Seasons - 5lb flue pressure test fail gauge was under 5lb
|