Final | 7/8/2019 | 7/11/2019 | 7/11/2019 | A | PASS |
Jack Reynolds
|
|
|
Call Carey ###-#### when on the way Phone #: ###-#### Inspection requested via web by John Bertram - final ok
|
Final | 6/27/2019 | 6/28/2019 | 6/28/2019 | A | NH |
Jack Reynolds
|
|
|
Sent photos of corrections to Jack''s cel phone Phone #: ###-#### Inspection requested via web by John Bertram - No access to home
|
Final | 6/18/2019 | 6/20/2019 | 6/20/2019 | A | FAIL |
Jack Reynolds
|
|
|
Contact Carey ###-#### Phone #: ###-#### Inspection requested via web by John Bertram - A/C fuses sizes are too big - gas lines for both water heater and furnace need sediment traps - common vent needs to be a wye and needs re configured where the smallest connector enters at the highest level
|