Permit Information
Permit NumberMEC19-02661
StatusFinaled
Name JEREMY WANDERS HVAC
Site Address 5431 N FIVE MILE RD
Project Name 
Customer Number9999
ePlanReviewNo
Description
Alteration or Repair: Turn existing garage into living space. 2.5 ton heat pump mini split installed. through wall pass through fan and transfer grill installed to bedroom. 30 CFM continuous fan installed in bath room for fresh air.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/11/20208/11/20208/11/2020PPASS
DetailsBrian Scoles
pass through fan in back bedroom wired up to be controlled by thermostat. Bathroom fan wired up to be on at 30 cfm continuously for fresh air.
Call home owner when you are on your way. Gary Carroll. ###-####. Phone #: ###-#### Inspection requested via web by jeremy wanders
Final5/20/20205/21/20205/21/2020AFAIL
DetailsBrian Scoles
owner occupied residence. Call home owner when you are on your way. Call Larry at ###-####. He has the Manual S compliance report. Thank you. Jeremy ###-#### Phone #: ###-#### Inspection requested via web by jeremy wanders- per man j need thermostat installed in bedroom and continuos fan need to be installed per man j- see notes on man j- recall in when these items are addressed-
Mec-Aging Inspection4/8/20204/8/20204/8/2020 CANC
DetailsBrian Scoles
WIP
Mec-Aging Inspection1/8/20201/8/20201/8/2020 FAIL
DetailsBrian Scoles
needs called in for final inspection- bld still open
Pressure Test7/24/20197/25/20197/25/2019APASS
DetailsBrian Scoles
New gauge installed on gas line. Thank you. Jeremy Phone #: ###-#### Inspection requested via web by jeremy wanders- 20lb gas pass
Pressure Test7/24/20197/24/20197/24/2019PFAIL
DetailsBrian Scoles
Jeremy Phone #: ###-####- gauge wont zero out
Rough-in6/26/20196/26/20196/26/2019PPASS
DetailsBrian Scoles
Nail plates installed. Phone #: ###-#### Inspection requested via web by jeremy wanders
Rough-in6/24/20196/25/20196/25/2019AFAIL
DetailsBen Livingston
Installed a mini split rough in box and ran a 3/4" PVC drain line. Phone #: ###-#### Inspection requested via web by jeremy wanders
condensate piping in wall studs within 1 1/2" to the edge needs nailplates
Rough-in6/20/20196/21/20196/21/2019AFAIL
DetailsBrian Scoles
rough in inspection for the pass through fan in the bed room. bath room fan, and transfer grills. mini split to be installed latter. Phone #: ###-#### Inspection requested via web by jeremy wanders- 3/4" condensate needs ran up to head location and remove flexable condensate in wall and maintain sloe in wall to outside of house