Information based on query as of Saturday, June 29, 2024.
Permit Information
Permit NumberMEC19-02922
StatusExpired
Name PROFLO HVAC & HOME INSPECTION
Site Address 3340 E ANEMONE CT
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Retro electric furnace and heat pump
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Mec-Aging Inspection7/27/20207/27/20207/27/2020 PASS
DetailsJack Reynolds
Doc Permit Expired ok
DOC - Permit Expired7/27/20207/27/20207/27/2020APASS
DetailsJack Reynolds
Doc Permit Expired ok permit not active
Mec-Aging Inspection4/27/20204/27/20204/27/2020 FAIL
DetailsJack Reynolds
Permit has not been active since 7-19-19. Schedule inspection with owner if ready. Permit will expire at next mechanical aging inspection if not asctive.
Mec-Aging Inspection1/27/20201/27/20201/27/2020 FAIL
DetailsJack Reynolds
Permit has not been active since 7-19-19. Schedule inspection with homeowner when corrections have been finished.
Final7/19/20197/19/20197/19/2019AFAIL
DetailsJack Reynolds
-secondary drain needs a wet switch installed
- line set insulation needs repaired in crawl and in garage where it is supported to the duct work
- condensate pump needs safety wired in to air handler
- line set penetration needs sealed and conduit penetration needs sealed at A/C
-
-
Final7/9/20197/15/20197/15/2019ANH
DetailsJack Reynolds
Inspection requested via web by Margie Rowe
- no access to home left notice on front door