Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMEC19-02985
StatusFinaled
Name ACCO ENGINEERED SYSTEMS
Site Address 250 S COLE RD
Project NameBuilding #7
Customer Number 
ePlanReviewNo
Description
Alteration: (Building #7) Replace 16 RTU's at this building. (Reference fees paid on MEC18-05024) //7-11-19 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/13/20198/13/20198/13/2019PPASS
DetailsBrian Scoles
Please contact Steve Kingsmore with any questions at ###-####. Phone #: ###-#### Inspection requested via web by Joshua Bennett- final ok
Final7/16/20197/17/20197/17/2019APART
DetailsBrian Scoles
Please contact Curt Osborne for access coordination and ladder. Please contact Curt Osborne at ###-#### Phone #: ###-#### Inspection requested via web by Joshua Bennett- need to strap all gas piping to supports that was extended or added on to on roof- rtu 18, 17, 4, 1 and 2 need to extend plumbing 3 feet higher than economizer and check metal snorkel between rtu 1 and 2 to close to economizer