Permit Information
Permit NumberMEC19-03314
StatusFinaled
Name THE HEATING AND COOLING COMPANY
Site Address 4365 N MORNINGGALE PL
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: Complete HVAC system with gas piping to 5 appliances
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/30/20201/30/20201/30/2020PPASS
DetailsBrian Scoles
Call for access to house Phone #: ###-#### Inspection requested via web by Bob Ferrin- final ok
Final1/28/20201/29/20201/29/2020PFAIL
DetailsBrian Scoles
Call for access Phone #: ###-#### Inspection requested via web by Bob Ferrin
1- w/h sinle wall flue doesnt have 6" clearance to sheetrock need to install 3" b vent adjustable 90 at ceiling to get clearances
2- need city approved man j onsite
3- need to seal line set penetration thru foundation vent outside at a/c location
Rough-in8/5/20198/5/20198/5/2019PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Bob Ferrin- r/i ok
Rough-in7/31/20198/1/20198/1/2019AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Bob Ferrin-
1- seal dryer duct to termination box
2- seal all spot welds on R/A cans
3- csst gas piping to range needs csst approved striker plates at ceiling and remove straps in wall can not be secured in walls
Pressure Test8/1/20198/1/20198/1/2019APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Bob Ferrin- 20lb gas pass-