Final | 10/15/2019 | 10/16/2019 | 10/16/2019 | A | PASS |
Jack Reynolds
|
|
|
Man j on furnace. Garage code is 6074. Phone #: ###-#### Inspection requested via web by Jon VanderStelt
- final ok
|
Final | 10/15/2019 | 10/15/2019 | 10/15/2019 | P | CANC |
Jack Reynolds
|
|
|
garage code 6074 Phone #: ###-#### >> Inspection requested via web by Jon VanderStelt Inspection cancelled from web by: Jon VanderStelt
|
Rough-in | 8/13/2019 | 8/13/2019 | 8/13/2019 | A | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Jon VanderStelto - R/I ok - need to check furnace to man J at final
|
Pressure Test | 8/13/2019 | 8/13/2019 | 8/13/2019 | A | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Jon VanderStelt -5lb flue pressure test ok
|
Rough-in | 8/9/2019 | 8/12/2019 | 8/12/2019 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Jon VanderStelt - need access to furnace model numbers - water flue has screws through inner pipe - return duct upstairs needs sealed - fix return flex outter liner upstairs - line set in crawl need supported and rips fixed - fresh air needs to be installed at furnace return plenum - nail plates at dryer vent and pvc flue - 5lb flue test fail - support gas line in attic near range
|
Pressure Test | 8/9/2019 | 8/12/2019 | 8/12/2019 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Jon VanderStelt - 5lb flue pressure test under 5lb - 20lb gas pressure test ok - tagged meter location
|