Final | 8/29/2019 | 8/30/2019 | 8/30/2019 | A | PASS |
Jack Reynolds
|
|
|
Jasper will be on site at 9:20. Please contact him with any questions. Phone #: ###-#### Inspection requested via web by Ted Dumont - 5lb flue pressure test ok - furnace ac coil co ok
|
Final | 8/28/2019 | 8/29/2019 | 8/29/2019 | A | NR |
Jack Reynolds
|
|
|
Please contact Jasper for access. We will be on site at 9:30 AM. Phone #: ###-#### Inspection requested via web by Ted Dumont - not ready and 5lb flue has a leak
|
Final | 8/27/2019 | 8/28/2019 | 8/28/2019 | A | FAIL |
Jack Reynolds
|
|
|
Please contact Jasper for access. He will be on site at 9:30 AM. Have a great day! Phone #: ###-#### Inspection requested via web by Ted Dumont - need to witness 5lb flue test - gas line needs sediment trap after shut off valve - secondary drain needs a wet switch installed - A/C needs to be 3ft away from gas meter regulator - co detectors installed upstairs and downstairs
|