Final | 12/8/2019 | 12/9/2019 | 12/9/2019 | A | PASS |
Brian Scoles
|
|
|
door code 5217 Phone #: ###-#### Inspection requested via web by Joseph Profitt- final ok
|
Final | 12/4/2019 | 12/4/2019 | 12/4/2019 | P | FAIL |
Brian Scoles
|
|
|
lock box code 5217 Phone #: ###-#### Inspection requested via web by Joseph Profitt- 1- need to level condenser pad 2- 2nd drain needs pvc 90 outside 3- need locking caps on service ports on a/c 4- need to seal lineset penetration thru skirting
recall in when completed
|
Rough-in | 9/23/2019 | 9/24/2019 | 9/24/2019 | A | PASS |
Brian Scoles
|
|
|
coil / ac / lineset / condensate drain line Phone #: ###-#### Inspection requested via web by Joseph Profitt- R/I ok- need to level condenser pad by final
|
Pressure Test | 9/23/2019 | 9/24/2019 | 9/24/2019 | A | PASS |
Brian Scoles
|
|
|
underground gas line Phone #: ###-#### Inspection requested via web by Joseph Profitt- 20lb gas pass- ok to backfill underground- tagged meter location
|
Pressure Test | 8/15/2019 | 8/16/2019 | 8/16/2019 | P | CANC |
Brian Scoles
|
|
|
inspection is for underground gas line Phone #: ###-#### Inspection requested via web by Joseph Profitt- mobile home not set yet
|
Rough-in | 8/15/2019 | 8/16/2019 | 8/16/2019 | P | CANC |
Brian Scoles
|
|
|
inspection is for line set and condensate drain from coil Phone #: ###-#### Inspection requested via web by Joseph Profitt- this mobile home not set yet
|