Final | 10/10/2019 | 10/11/2019 | 10/11/2019 | A | PASS |
Jack Reynolds
|
|
|
Garage code is 2468 Phone #: ###-#### Inspection requested via web by JOSE DUARTE
- final ok
|
Final | 10/8/2019 | 10/8/2019 | 10/8/2019 | A | FAIL |
Jack Reynolds
|
|
|
Garage code is 2468 Phone #: ###-#### Inspection requested via web by JOSE DUARTE
- need air balance report onsite - momentum needs to finish filling out information sticker at electrical panel
|
Rough-in | 8/19/2019 | 8/19/2019 | 8/20/2019 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by JOSE DUARTE
|
Rough-in | 8/19/2019 | 8/19/2019 | 8/19/2019 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by JOSE DUARTE - water heater flue pipe needs replaced screws penetrated inner liner - both insulation shields need to maintain 1" clearances around flue - fresh air duct needs connected to return plenum - exhaust fans need installed/ ducting installed
|
Pressure Test | 8/19/2019 | 8/19/2019 | 8/19/2019 | A | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by JOSE DUARTE - 20lb gas pressure test ok - tagged meter location
|