Final | 11/22/2019 | 11/22/2019 | 11/22/2019 | P | PASS |
Brian Scoles
|
|
|
please reach out to Todd if you have any questions ###-#### 2nd contact would be Glen ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Yvonne Bowman- 2 RTU finals ok- gas piing ok- smoke detector installed both units- weather tight whips installed
|
Final | 10/14/2019 | 10/15/2019 | 10/15/2019 | A | FAIL |
Jack Reynolds
|
|
|
This is a final/final. Please contact Glen with any questions ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Yvonne Bowman - both units need wheather tight conduits installed - gas lines need supported and sediment traps and test ports installed - need to prove 7.5 ton unit has smoke shut down
|