Mec-Aging Inspection | 6/16/2020 | 6/16/2020 | 6/16/2020 | | FAIL |
Jack Reynolds
|
|
|
Permit has not been active since failing inspection on 8-29-19. Schedule final inspection with owner when ready. Permit will expire at next mechanical aging inspection if not active.
|
Mec-Aging Inspection | 3/17/2020 | 3/17/2020 | 3/17/2020 | | FAIL |
Jack Reynolds
|
|
|
Permit has not been active since failing on 8-29-19. Need to check functionality of smoke detectors on RTU's. Schedule inspection with owner when work is finished.
|
Final | 8/26/2019 | 8/29/2019 | 8/29/2019 | P | FAIL |
Jack Reynolds
|
|
|
INSTALLER GERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt - new RTU needs smoke detection shut down installed either using smoke detectors installed in return duct or using building fire alarm system to shut down RTU
|
Pressure Test | 8/26/2019 | 8/29/2019 | 8/29/2019 | P | PASS |
Jack Reynolds
|
|
|
INSTALLER GERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt - 60lb gas pressure test ok to new RTU
|