Final | 12/3/2019 | 12/3/2019 | 12/3/2019 | P | PASS |
Chad Schwendiman
|
|
|
Please call Bill at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Rough-in | 10/22/2019 | 10/22/2019 | 10/22/2019 | P | PASS |
Chad Schwendiman
|
|
|
Please call Rick at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Okay to sheetrock the hard lid ceilings
|
Rough-in | 10/10/2019 | 10/10/2019 | 10/10/2019 | P | FAIL |
Chad Schwendiman
|
|
|
Please call Dan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Need access to service and remove equipment above hard lid ceilings. Need a signed letter from the Structural Engineer verifying the top of the hard lid ceiling will be supported enough to use as a working platform as it is. Approved plans show for the ceiling to be framed in 18ga studs, it was installed with 20ga studs. Need to support return air sound boots from the structure above.
|
Rough-in | 10/9/2019 | 10/11/2019 | 10/10/2019 | A | CANC |
Chad Schwendiman
|
|
|
Are we good to cover? Please call Dan at least 30 min prior to inspection, thank you! Phone #: ###-#### >> Inspection requested via web by Rhonda Marcum Inspection cancelled from web by: Rhonda Marcum
|