Permit Information
Permit NumberMEC19-04041
StatusFinaled
Name RIGHT NOW INC HTG & COOLING
Site Address 3880 N PATRICIA LN
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Replace AC
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/16/201910/18/201910/18/2019PPASS
DetailsBrian Scoles
Please inspect from 12;30-4. Homeowner Fauzia Aziz ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- a/c coil co locking caps ok
Final10/4/201910/11/201910/11/2019PNH
DetailsJack Reynolds
Please inspect after 1 PM. Fauzia Aziz ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- no access to home left notice on front door
Final9/13/20199/20/20199/20/2019PFAIL
DetailsBrian Scoles
Homeowner Fauzia Aziz ###-####. Phone #: ###-#### Inspection requested via web by Mary LaFayette- need to install secondary wet switch- need to firecaulk primary drain in furnace closet at floor- need to change breaker in panel to meet min/max rating on a/c- has 15 amps now and minimum is 17.6- will need electrical permit issued by final for breaker swap