Final | 4/17/2020 | 4/17/2020 | 4/17/2020 | P | PASS |
Ben Livingston
|
|
|
Rob will send pictures to verify equipment Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|
Final | 4/2/2020 | 4/2/2020 | 4/2/2020 | A | PART |
Ben Livingston
|
|
|
TCO Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Temp C.O.
|
Final | 4/1/2020 | 4/1/2020 | 4/1/2020 | P | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - condencers need locking caps -need air balance reports - duct and low voltage wire is laying on the ground in the crawl, duct also needs insulation
|
Final | 3/30/2020 | 3/31/2020 | 3/31/2020 | A | CANC |
Ben Livingston
|
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN Inspection cancelled from web by: GREGORY ANDERSEN
|
Final | 3/27/2020 | 3/30/2020 | 3/30/2020 | A | CANC |
Ben Livingston
|
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN Inspection cancelled from web by: GREGORY ANDERSEN
|
Final | 3/26/2020 | 3/27/2020 | 3/27/2020 | P | CANC |
Ben Livingston
|
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN Inspection cancelled from web by: GREGORY ANDERSEN
|
Rough-in | 11/11/2019 | 11/12/2019 | 11/12/2019 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|
Rough-in | 11/8/2019 | 11/8/2019 | 11/8/2019 | P | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - all bedrooms need return path -
|
Pressure Test | 11/8/2019 | 11/8/2019 | 11/8/2019 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - 20lb - - 5lb x4 -
|
Pressure Test | 11/6/2019 | 11/7/2019 | 11/7/2019 | A | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
- gauge didnt zero out - - gas flex needs factory approved stricker plates - - need sleave at fireplace cabinet -
|
Rough-in | 11/6/2019 | 11/7/2019 | 11/7/2019 | A | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - need approved manual j -
|