Final | 1/29/2020 | 1/31/2020 | 1/31/2020 | A | PASS |
Jack Reynolds
|
|
|
Please call Glenn 1st thing in the morning with an ETA so that he can meet you onsite for access. ###-####
Alt# Yvonne ###-#### if needed. Phone #: ###-#### Inspection requested via web by Yvonne Bowman - final ok
|
Final | 1/7/2020 | 1/8/2020 | 1/8/2020 | A | FAIL |
Jack Reynolds
|
|
|
Santiago Phone #: ###-#### - need access to roof to inspect outdoor unit and venting - condensate needs to be per the approved prints/min 3/4 pvc - return and supply ducting is not per approved prints. return missing duct/supply duct is missing all dampers including fresh air duct. - electric heater in bathroom is missing
|
Rough-in | 11/26/2019 | 11/26/2019 | 11/26/2019 | P | PASS |
Jack Reynolds
|
|
|
please contact Glen with any questions Phone #: ###-#### Inspection requested via web by Yvonne Bowman - bathroom hard lid cover ok
|
Rough-in | 11/25/2019 | 11/25/2019 | 11/25/2019 | P | FAIL |
Jack Reynolds
|
|
|
Please contact Glen with any questions. ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Yvonne Bowman - exhaust fan ducting in bathroom needs sealed for cover of ceiling
|
Rough-in | 11/15/2019 | 11/15/2019 | 11/15/2019 | P | PART |
Jack Reynolds
|
|
|
Please contact Glen with any issues ###-#### Phone #: ###-#### Inspection requested via web by Yvonne Bowman - partial R/I ok on exhaust and fresh air ducting through roof - all mech work will be exposed and can be seen once installed
|