Final | 1/6/2020 | 1/7/2020 | 1/7/2020 | A | PASS |
Brian Scoles
|
|
|
CORRECTION MADE MAN J INSIDE INFORMATION BIN BY ELECTRICAL PANEL LOCK BOX CODE 0124 Phone #: ###-#### Inspection requested via web by Oleg Chervak
|
Final | 1/3/2020 | 1/3/2020 | 1/3/2020 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak 1- seal exterior gas line penetration at meter 2- condensate to washer box needs completed 3- approved man j onsite
|
Final | 1/3/2020 | 1/3/2020 | 1/3/2020 | P | CANC |
Brian Scoles
|
|
|
GARAGE CD 1234 Phone #: ###-#### >> Inspection requested via web by Oleg Chervak Inspection cancelled from web by: Oleg Chervak
|
Rough-in | 10/2/2019 | 10/3/2019 | 10/3/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I ok
|
Pressure Test | 10/2/2019 | 10/3/2019 | 10/3/2019 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- already passed
|
Rough-in | 10/1/2019 | 10/2/2019 | 10/2/2019 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- corrections not all made- see notice sliding door window
|
Pressure Test | 10/1/2019 | 10/2/2019 | 10/2/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak
|
Rough-in | 10/1/2019 | 10/1/2019 | 10/1/2019 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- wont be ready by time i come back by- reschedule
|
Rough-in | 9/30/2019 | 10/1/2019 | 10/1/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 1- framing needs completed around b vent 2nd floor and draftstop installed correctly 2- dryer duct to termination box needs sealed 3- need 6" fresh air ran and maintain 10 feet from exhaust 4- exhaust fan shall terminate 4 feet from property line 2nd flood 5 need all bare metal in attic insulated off furnace supply and R/A
|
Pressure Test | 9/30/2019 | 10/1/2019 | 10/1/2019 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass- tagged meter location
|