Final | 5/29/2020 | 5/29/2020 | 5/29/2020 | A | PASS |
Brian Scoles
|
|
|
Please call installer on way at ###-#### and call Ryan with questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- final ok
|
Conference | 5/29/2020 | 5/29/2020 | 5/29/2020 | A | PASS |
Brian Scoles
|
|
|
To Witness duct blast, please call installer on way at ###-#### and call Ryan with questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- duct blast test pass
|
Final | 5/28/2020 | 5/28/2020 | 5/28/2020 | A | NR |
Brian Scoles
|
|
|
Waiting for approved manual J from city, please homeowner 30 minutes in advance for access at ###-#### call Ryan with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum 1- need approved man j onsite 2- need to remove enclosure around range duct to verify seal and ducting 3- need to witness duct blast test 4- need to filter outside air in attic since has filter grills installed 5- need locking caps on condenser
schedule duct blast test when ready
|
Mec-Aging Inspection | 4/27/2020 | 4/27/2020 | 4/27/2020 | | CANC |
Brian Scoles
|
|
|
needs called in for final when ready- WIP
|
Rough-in | 10/17/2019 | 10/17/2019 | 10/17/2019 | A | PASS |
Brian Scoles
|
|
|
Please call Ryan with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- R/I ok- equipment not set check at final- left sticker in YMC folder on plan table
|
Rough-in | 10/15/2019 | 10/15/2019 | 10/15/2019 | P | FAIL |
Brian Scoles
|
|
|
Please call James with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- 1- need to fix all rips and tears in arma flex in wall and attic 2- need to install 18" R/A in hallway per approved man j in hallway
left notice front of YMC folder
|
Rough-in | 10/4/2019 | 10/7/2019 | 10/7/2019 | A | FAIL |
Brian Scoles
|
|
|
Please call Ryan with any questions or concerns at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum 1- need to resubmit man j for the way ducting is ran now or run per approved man j- supply and R/A duct missing or ran different 2- is W/H flue solid core pvc for tanlless water heater can not see labeling on PVC? needs vent thru roof to maintain 10' from property line and maintain 10' or 3' from outside air intake
left notice YMC folder
|
Pressure Test | 10/7/2019 | 10/7/2019 | 10/7/2019 | A | PASS |
Brian Scoles
|
|
|
Please call Ryan with any questions or concerns at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- 20 lb gas pass- tagged meter location
|
Rough-in | 10/4/2019 | 10/4/2019 | 10/4/2019 | A | FAIL |
Brian Scoles
|
|
|
Please call Ryan with any question or concerns at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- no corrections have been made
|
Rough-in | 10/3/2019 | 10/3/2019 | 10/3/2019 | A | FAIL |
Brian Scoles
|
|
|
Please call Ryan with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- 1- need city approved man j onsite 2- gas test failed 3- need top seal supplu and R/A boots on all spot weld seams 4- need to seal and insulate supply reducer and insulate in attic above living room 5- need to insulate bare metal in attic on supply trunk above master bath 6- water heater flue or is it electric?
left correction notice in YMC folder on print table
|
Pressure Test | 10/3/2019 | 10/3/2019 | 10/3/2019 | A | FAIL |
Brian Scoles
|
|
|
Please call Ryan with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- gas test failed gauge at 12 psi
|