Permit NumberMEC19-04530
StatusFinaled
Name YMC INC
Site Address 6140 W CURTISIAN AVE
Project NameSARMC EP Lab Remodel
Customer Number2107941
ePlanReviewNo
Description
Alteration: Install RTU, Split systems, FSD''s and duct work.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/16/20206/17/20206/17/2020APASS
DetailsBrian Scoles
Please call Ted at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda - final ok- card signed
Rough-in6/2/20206/2/20206/2/2020PPASS
DetailsBrian Scoles
Please call Lee at least 30 min prior to inspection, thank you!
Phone #: ###-#### Inspection requested via web by Rhonda Marcum- linesets exterior duct chase ok- supports ok- ok to cover exterior structure
Rough-in5/20/20205/20/20205/20/2020PPART
DetailsBrian Scoles
Cover, please call Ted at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum- exterior duct work and penetration into building ok- need to see linesets ran and supports next inspection before covering exterior studs
Mec-Aging Inspection5/12/20205/12/20205/12/2020 CANC
DetailsBrian Scoles
needs called in for inspection when ready- WIP
Rough-in2/11/20202/11/20202/11/2020PPART
DetailsBrian Scoles
Please call Ted at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum- seal on duct ok- ok to insulate to server room- will need approved drawings sent to city for review on new routing on exterior wall and roof by next inspection with approved prints onsite
Rough-in1/3/20201/6/20201/6/2020APASS
DetailsBen Livingston
Please call Ted at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- 3 NEW FIRE SMOKE DAMPERS IN CORRIDOR ANGLES OKAY -
Rough-in12/23/201912/24/201912/24/2019APART
DetailsJack Reynolds
Partial cover, please call Ted at least 30 min prior to inspection, thank you and Merry Christmas. Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- three dampers added on north side clearances ok for angles
- duct seal on 18" supply in hallway between two dampers ok for insulation
- main duct still needs ran out to RTU
-Partial cover ok leave tiles out where HVAC work needs to be seen for inspection
Rough-in11/13/201911/14/201911/14/2019APASS
DetailsBrian Scoles
Please call Ted at leastt 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum- R/I on 3 f/s damper clearances ok- ok for angles- lab area only ok to cover ceiling- need to vderify if more f/s dampers are needed in 1 hour wall- Ted will get with engineer about this
Conference11/7/201911/8/201911/8/2019ADONE
DetailsBrian Scoles
Please call Ted at least 30 min prior to inspection, thank you!! Phone #: ###-#### Inspection requested via web by Rhonda Marcum- discussed fire smoke damper install- 1 hour wall so dampers can be 1 side angle per installation instructions R/A damper only
Rough-in11/6/201911/7/201911/7/2019APASS
DetailsChad Schwendiman
Please call Ted at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum