Permit Information
Permit NumberMEC19-04591
StatusFinaled
Name WESTERN HEATING & A/C
Site Address 3423 S LONGLEAF AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: RUN GAS LINE FROM TEE IN CRAWL TO TANKLESS WATER HEATER
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/23/201910/23/201910/23/2019PPASS
DetailsJack Reynolds
Inspection requested via web by Aaron Alandt
- 20lb gas pressure test ok
- IGC is taking responsibility on gas meter size in relation to equipment loads
Final10/21/201910/22/201910/22/2019APART
DetailsJack Reynolds
Called Intermountain Gas and verified meter was large enough. They said it was but they would swing by tomorrow to verify the spring. The gas pipe is 1 1/4 all the way to the crawl and then reduces to 1" then 3/4 to tankless. Phone #: ###-#### Inspection requested via web by Aaron Alandt
- need verification from gas company on meter being sized for load
- if gas piping system is being updated to a high pressure system need to see a 60lb gas pressure test and regulators installed
Pressure Test10/14/201910/21/201910/21/2019PFAIL
DetailsJack Reynolds
INSTALLER JOHN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- 20lb gas pressure test ok
- gas meter needs to be verified for total load with new tankless water heater
- verify gas pipe sizing