Permit NumberMEC19-04662
StatusFinaled
Name ICON AIR
Site Address 7017 E FAREWELL BEND CT
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: Installing HVAC
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/26/20202/27/20202/27/2020APASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Randy Hart
- final ok
Pressure Test2/21/20202/26/20202/26/2020ACANC
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Randy Hart
- this site has already passed pressure tests
Rough-in2/21/20202/26/20202/26/2020ACANC
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Randy Hart
- this site has already passed R/I
Rough-in1/2/20201/2/20201/2/2020PPASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Randy Hart
- R/I ok
Rough-in12/19/201912/20/201912/20/2019PFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Randy Hart
- Talked with builder onsite about having a conference inspection with the building inspector about the floor joist that was cut.
- will not pass R/I until joist is checked by building inspector.
- re inspection fee applied
Rough-in12/18/201912/19/201912/19/2019PFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Randy Hart
- Approved Man J onsite
- General contractor needs to have building inspector check floor joist that was cut next to the water heater flue
Pressure Test12/18/201912/19/201912/19/2019PPASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Randy Hart
- 5lb flue pressure test ok
Rough-in12/12/201912/18/201912/18/2019AFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Randy Hart
- approved Man j onsite
- line set insulation needs repaired
- water heater flue needs insulation sheild centered to maintain 1" clearances
- 5lb flue pressure test
- supply boots in garage need insulated
- floor joist in garage next to water heater needs checked by building inspector
Pressure Test12/12/201912/18/201912/18/2019AFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Randy Hart
- 5lb flue pressure test fail
- 20lb gas pressure test ok
- tagged meter location