Permit Information
Permit NumberMEC19-04898
StatusFinaled
Name PERFORMANCE MECHANICAL INC
Site Address 1517 S LEADVILLE AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: New HVAC system// added range hood and fire place 2-20-20 tch
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/3/20203/4/20203/4/2020APASS
DetailsJack Reynolds
Thank you Phone #: ###-#### Inspection requested via web by Aaron Johns
- final ok
Rough-in2/26/20202/27/20202/27/2020APASS
DetailsJack Reynolds
Greg Phone #: ###-####
- R/I ok on enclosure of b vent
- will need to see b vent tee installed at bottom of vent and access door in enclosure by final
Rough-in2/19/20202/19/20202/19/2020PPART
DetailsJack Reynolds
301
- vent pipe clearances to framing ok
- need to see clearances with insulation installed
- vent piping specs should be followed for enclosure. having an access door to the vent and a b vent tee at the bottom for clean out
Final2/12/20202/12/20202/12/2020PFAIL
DetailsJack Reynolds
Thank you Phone #: ###-#### Inspection requested via web by Aaron Johns
- 2428.2.9 IRC 2012 any b vent exposed more than 5' to the outdoors shall be enclosed or chased and insulated to not less than R-8
/ vent manufactures specs for being in an enclosure- need to add range and fireplace to permit
- need air balance report
- electrical needs finished at furnace and A/C
- b vent needs 1" clearances
- line set needs UV protection and locking installed on A/C
- all penetrations need sealed
- water heater needs sediment trap in gas line
Rough-in11/6/201911/7/201911/7/2019PPASS
DetailsJack Reynolds
if you could call in advance so I can unlock the building that would be great it might be unlocked anyway thank you. Troy approved the new manual J and we have a new fire place installed and the duct seal done see you tomorrow Phone #: ###-#### Inspection requested via web by Aaron Johns
- fireplace and HVAC R/I ok
- need to add fireplace to permit
Rough-in11/1/201911/4/201911/4/2019AFAIL
DetailsJack Reynolds
Thank you Phone #: ###-#### Inspection requested via web by Aaron Johns
- Man j needs updated and approved by the City
- fllor boots need sealed to floor
- range vent needs sealed
- If fireplace is staying it needs an inspection and installation instructions onsite
Pressure Test11/4/201911/4/201911/4/2019APASS
DetailsJack Reynolds
Thank you Phone #: ###-#### Inspection requested via web by Aaron Johns
- 20lb gas pressure test ok
- tagged meter location
Rough-in10/30/201910/31/201910/30/2019PCANC
DetailsJack Reynolds
Thank you Phone #: ###-#### >> Inspection requested via web by Aaron Johns Inspection cancelled from web by: Aaron Johns