Mec-Aging Inspection | 6/11/2020 | 6/11/2020 | 6/11/2020 | | FAIL |
Jack Reynolds
|
|
|
Permit failed inspection on 1-14-20. Schedule inspection with owner if corrections have been made.
|
Final | 1/9/2020 | 1/14/2020 | 1/14/2020 | P | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by James Cox - not an approved clearance reduction installed - install b vent to achieve clearances
|
Final | 1/7/2020 | 1/8/2020 | 1/8/2020 | P | NH |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by James Cox - no access to home talked with contractor via phone call
|
Final | 12/17/2019 | 12/20/2019 | 12/20/2019 | A | NH |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by James Cox - no access to home left notice on front door
|
Final | 11/12/2019 | 11/19/2019 | 11/19/2019 | P | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by James Cox - furnace flue needs 6" clearances or b vent installed with 1' clearances to condensate drain and pump tubing - secondary drain on coil needs wet switch installed
|