Final | 7/9/2020 | 7/9/2020 | 7/9/2020 | P | PASS |
Jack Reynolds
|
|
|
benny - Virtual inspection Phone #: ###-#### Brad
- final ok
|
Mec-Request for Extension | 6/24/2020 | 6/25/2020 | 6/25/2020 | A | PASS |
Jack Reynolds
|
|
|
Talk to Jack Reynolds and he said to get a Mec-Extension Inspection requested via web by Benny Arreola - Mechanical Extension ok
|
Mec-Aging Inspection | 6/24/2020 | 6/24/2020 | 6/24/2020 | | FAIL |
Jack Reynolds
|
|
|
Permit has not been active since 12-11-19 when it passed a R/I inspection. Schedule final inspection if work is finished.
|
Rough-in | 12/10/2019 | 12/11/2019 | 12/11/2019 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Benny Arreola - R/I ok - still need to check Man J to equipment and verify location/ size of attic access to furnace by final
|
Pressure Test | 12/10/2019 | 12/11/2019 | 12/11/2019 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Benny Arreola -60lb gas pressure test ok - tagged meter
|
Rough-in | 12/9/2019 | 12/10/2019 | 12/10/2019 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Benny Arreola - need to access to furnace and equipment in attic - man J approved and onsite - CSST near range needs full strikers plates installed in wall studs - where is mechanically vented crawls intake coming from within the house?
|
Pressure Test | 12/9/2019 | 12/10/2019 | 12/10/2019 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Benny Arreola - gas pressure test needs to be a 60lb test on a 100lb
|