Final | 1/24/2020 | 1/31/2020 | 1/31/2020 | P | PASS |
Brian Scoles
|
|
|
PLEASE CALL HOMEOWNER JESSICA WHEN 30 MINS IN ROUTE - Phone #: ###-#### Inspection requested via web by Rick Montgomery- final ok
|
Final | 11/21/2019 | 11/22/2019 | 11/22/2019 | P | FAIL |
Brian Scoles
|
|
|
PLEASE CALL HOMEOWNER JESSICA WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace a/c coil co ok- bubble wrap insulation on R/A needs 3/4" air gap per installation instructions has no gap- need to install the locking caps left by the service ports- send pic for reinspect
|