Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberMEC19-05219
StatusFinaled
Name DIAMOND HEATING AND COOLING
Site Address 1368 E OAKRIDGE DR
Project Name 
Customer Number18919526
ePlanReviewNo
Description
Alteration or Repair: RUNNING 40 FT OF GAS LINE FROM NEW GAS METER TO HOME. INSTALLING 80% GAS FURNACE AND 13 SEER AC COIL
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/5/201912/6/201912/6/2019PPASS
DetailsJack Reynolds
WE ARE DOING CORRECTIONS EARLY AFTERNOON FOR THIS JACK- IF YOU CAN MOVE THIS CLOSER TO END OF DAY WE WILL HAVE EVERYTHING CORRECTED AND DONE. PLEASE CALL KATIE WHEN YOUR IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery
- final ok
Final11/26/201911/27/201911/27/2019PFAIL
DetailsJack Reynolds
please call Katie when 30 mins in route- also we have final for plumbing- PLM19-04977 Phone #: ###-#### Inspection requested via web by Rick Montgomery
- new common vent needs an insulation shield installed in attic
- venting in attic needs slope
- gas line penetration needs sealed
Pressure Test11/19/201911/20/201911/20/2019APASS
DetailsJack Reynolds
GAS LINE RAN IS UNDER PRESSURE AND READY FOR INSPECTION- GAS LINE IS RAN ON OUTSIDE ACCESS AND YOU HAVE PERMISSION TO CHECK ANYTIME. I LEFT MY PHONE NUMBER FOR ANY QUESTIONS OR CONCERNS- MY NAME IS STEVE DALE WITH DIAMOND Phone #: ###-#### Inspection requested via web by Rick Montgomery
- 20lb gas pressure test ok
- tagged meter location