Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberMEC19-05528
StatusFinaled
Name ECONOMY HEATING AND AIR
Site Address 4307 W FREEMONT ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: pressure test for gas line
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled12/17/201912/17/201912/17/2019PPASS
DetailsJack Reynolds
final ok
Pressure Test12/17/201912/17/201912/17/2019PPASS
DetailsJack Reynolds
call ###-#### for any questions Phone #: ###-#### Inspection requested via web by brett hoopes
- 20lb gas pressure test
- tagged meter
Pressure Test12/6/201912/6/201912/6/2019PFAIL
DetailsJack Reynolds
gage on east sie of house,call if lock box is needed, gas line is visable in crawl outsideback yard access Phone #: ###-#### Inspection requested via web by brett hoopes
-gas piping outside needs to be 3.5" above ground. Where gas line enters basment gas line also needs to be 3.5" above ground
- gas line penetration needs 10mill tape installed and penetration sealed
-gas line needs supported in basement and outside of house