Final | 2/4/2020 | 2/5/2020 | 2/5/2020 | A | PASS |
Brian Scoles
|
|
|
Garage code 2468 Phone #: ###-#### Inspection requested via web by Arielle Hendricks- final ok
|
Final | 1/29/2020 | 2/3/2020 | 2/3/2020 | A | FAIL |
Brian Scoles
|
|
|
Garage Code 2468 - Builder ###-#### - HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks 1- need city approved man j onsite 2- duct blast test failed according to sticker on electrical panel allowed 81 cfm results 86 cfm need to fix 3- need air balance report onsite 4- water heater flue needs 3 screws per joint and open hole at china cap needs screw installed
|
Rough-in | 12/16/2019 | 12/17/2019 | 12/17/2019 | A | PASS |
Jack Reynolds
|
|
|
Garage Code 2468 - Builder ###-#### - HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - R/I ok
|
Pressure Test | 12/13/2019 | 12/16/2019 | 12/16/2019 | A | PASS |
Chad Schwendiman
|
|
|
Garage Code 2468 - Builder ###-#### - HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - 20lb gas 5lb flue
|
Rough-in | 12/13/2019 | 12/16/2019 | 12/16/2019 | A | FAIL |
Chad Schwendiman
|
|
|
Garage Code 2468 - Builder ###-#### - HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - Still need to fix rips in armaflex
|
Pressure Test | 12/12/2019 | 12/13/2019 | 12/13/2019 | A | FAIL |
Chad Schwendiman
|
|
|
Garage Code 2468 - Builder ###-#### - HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - Both gas and flue pressure tests fail
|
Rough-in | 12/12/2019 | 12/13/2019 | 12/13/2019 | A | FAIL |
Chad Schwendiman
|
|
|
Garage Code 2468 - Builder ###-#### - HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - 1) Need to fix rips in aramflex 2) Exhaust fans not connected to vent 3) Supply branch to kitchen is undersized 4) Need to seal seam on range vent
|
Pressure Test | 12/11/2019 | 12/12/2019 | 12/12/2019 | A | NR |
Chad Schwendiman
|
|
|
Garage Code 2468 - Builder ###-#### - HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
|
Rough-in | 12/11/2019 | 12/12/2019 | 12/12/2019 | A | NR |
Chad Schwendiman
|
|
|
Garage Code 2468 - Builder ###-#### - HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
|