Final | 4/23/2020 | 4/23/2020 | 4/23/2020 | P | PASS |
Jack Reynolds
|
|
|
2583 is garage code Inspection requested via web by Loren Bailey - final ok
|
Final | 4/22/2020 | 4/22/2020 | 4/22/2020 | P | FAIL |
Jack Reynolds
|
|
|
2583 Garage code Phone #: ###-#### Inspection requested via web by Loren Bailey - line set insulation at outdoor unit needs repaired and UV protected
|
Final | 4/21/2020 | 4/22/2020 | 4/22/2020 | A | CANC |
Jack Reynolds
|
|
|
Phone #: ###-#### >> Inspection requested via web by Loren Bailey Inspection cancelled from web by: Loren Bailey
|
Final | 4/20/2020 | 4/21/2020 | 4/20/2020 | A | CANC |
Jack Reynolds
|
|
|
Phone #: ###-#### >> Inspection requested via web by Loren Bailey Inspection cancelled from web by: Loren Bailey
|
Rough-in | 1/2/2020 | 1/2/2020 | 1/2/2020 | P | PASS |
Jack Reynolds
|
|
|
Fixed problems from inspection report. Phone #: ###-#### Inspection requested via web by Loren Bailey - R/I ok
|
Rough-in | 12/30/2019 | 12/31/2019 | 12/31/2019 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Loren Bailey - Still need to brace B-vent to maintain 1" clearance between it and the insulation shield
|
Rough-in | 12/17/2019 | 12/17/2019 | 12/17/2019 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Loren Bailey - Gas pressure test fail, Need 1" clearance between b-vent and insulation shield. Equipment installed doesn't match the approved manual J
|