Final | 5/13/2020 | 5/14/2020 | 5/14/2020 | A | PASS |
Ben Livingston
|
|
|
Screened- Virginia Phone #: ###-####
|
Final | 5/11/2020 | 5/12/2020 | 5/12/2020 | A | FAIL |
Ben Livingston
|
|
|
call for access-Virgina *screened** Phone #: ###-#### - lineset needs uv protection
|
Rough-in | 1/9/2020 | 1/10/2020 | 1/10/2020 | A | PASS |
Ben Livingston
|
|
|
Please call. Virginia 2085702753. I apologize the plumber was supost to add a pump in the crawl ..but ended up running the pipe up to the washer boxs..i fixed it ...sorry...thanks Phone #: ###-#### Inspection requested via web by virginia quijano
|
Rough-in | 1/9/2020 | 1/9/2020 | 1/9/2020 | P | FAIL |
Ben Livingston
|
|
|
virginia Phone #: ###-#### - condensate needs to be graded, it will not drain like that, also needs nailplates -
|
Rough-in | 1/8/2020 | 1/9/2020 | 1/9/2020 | A | FAIL |
Ben Livingston
|
|
|
vIRGINIA Phone #: ###-#### - need to run condensate to an approved discharge location -
|
Rough-in | 12/27/2019 | 12/30/2019 | 12/30/2019 | A | FAIL |
Ben Livingston
|
|
|
Call Virginia Sanchez Phone #: ###-#### Inspection requested via web by virginia quijano - fresh air isnot installed per approved print - - flex tubing not approved condensate material - - all duct needs tobe sealed - - duct insulation needs vapor barrier -
|
Pressure Test | 12/30/2019 | 12/30/2019 | 12/30/2019 | P | PASS |
Ben Livingston
|
|
|
Call Virginia Sanchez Phone #: ###-#### Inspection requested via web by virginia quijano - 5lb flue -
|
Rough-in | 12/20/2019 | 12/23/2019 | 12/23/2019 | A | FAIL |
Ben Livingston
|
|
|
call for access // Virginia Phone #: ###-#### - 12" return and fresh air shows a fire damper, this also needs tobe fully ducted , install per key note 1 on plans- - water heater needs combustion air - - all duct in crawl needs insulation - - flex tubing not approved condensate material - - need to put flue on pressure test -
|