Permit Information
Permit NumberMEC19-05739
StatusFinaled
Name VICS HVAC
Site Address 6101 N PIERCE PARK LN
Project NameIdaho ATC Group Home
Customer Number 
ePlanReviewNo
Description
replace the furnace and A/C, changing out duct work, and adding bath fans.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/13/20205/14/20205/14/2020APASS
DetailsBen Livingston
Screened- Virginia Phone #: ###-####
Final5/11/20205/12/20205/12/2020AFAIL
DetailsBen Livingston
call for access-Virgina *screened** Phone #: ###-####
- lineset needs uv protection
Rough-in1/9/20201/10/20201/10/2020APASS
DetailsBen Livingston
Please call. Virginia 2085702753. I apologize the plumber was supost to add a pump in the crawl ..but ended up running the pipe up to the washer boxs..i fixed it ...sorry...thanks Phone #: ###-#### Inspection requested via web by virginia quijano
Rough-in1/9/20201/9/20201/9/2020PFAIL
DetailsBen Livingston
virginia Phone #: ###-####
- condensate needs to be graded, it will not drain like that, also needs nailplates -
Rough-in1/8/20201/9/20201/9/2020AFAIL
DetailsBen Livingston
vIRGINIA Phone #: ###-####
- need to run condensate to an approved discharge location -
Rough-in12/27/201912/30/201912/30/2019AFAIL
DetailsBen Livingston
Call Virginia Sanchez Phone #: ###-#### Inspection requested via web by virginia quijano
- fresh air isnot installed per approved print -
- flex tubing not approved condensate material -
- all duct needs tobe sealed -
- duct insulation needs vapor barrier -
Pressure Test12/30/201912/30/201912/30/2019PPASS
DetailsBen Livingston
Call Virginia Sanchez Phone #: ###-#### Inspection requested via web by virginia quijano
- 5lb flue -
Rough-in12/20/201912/23/201912/23/2019AFAIL
DetailsBen Livingston
call for access // Virginia Phone #: ###-####
- 12" return and fresh air shows a fire damper, this also needs tobe fully ducted , install per key note 1 on plans-
- water heater needs combustion air -
- all duct in crawl needs insulation -
- flex tubing not approved condensate material -
- need to put flue on pressure test -