Permit Information
Permit NumberMEC19-05758
StatusFinaled
Name A-1 HEATING & AIR CONDITIONING
Site Address 3256 E EASTGATE DR
Project Name 
Customer NumberR6191134
ePlanReviewNo
Description
Alteration or Repair: Remove and reinstall/relocating furnace and water heater. Misc duct work. venting for range
R6191134 // 1-6-20 Adding a bath and dryer exhaust TCH
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/11/20203/12/20203/12/2020APASS
DetailsJack Reynolds
*There''s a key on top of the meter - Christian ###-#### - HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- final ok
Final3/10/20203/11/20203/11/2020AFAIL
DetailsJack Reynolds
Chris ###-####
HVAC ###-####
*There is a key on top of the meter Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- common b vent needs 1" clearances to wood stud and sheetrock
Final1/29/20201/29/20201/29/2020PNR
DetailsJack Reynolds
Christian - 1-###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- not ready
Rough-in1/29/20201/29/20201/29/2020PPASS
DetailsJack Reynolds
Christian - 1-###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- R/I ok
Rough-in1/22/20201/22/20201/22/2020PNR
DetailsJack Reynolds
Christian ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- not ready
- exhaust fan still not hooked up
- range vent will need to be sealed by final ok project
Rough-in1/16/20201/17/20201/16/2020ACANC
DetailsJack Reynolds
Builder ###-####
HVAC ###-#### Phone #: ###-#### >> Inspection requested via web by Arielle Hendricks Inspection cancelled from web by: Arielle Hendricks
Rough-in1/14/20201/15/20201/15/2020ANR
DetailsJack Reynolds
Chris ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- not ready exhaust fan in basement not connected to ducting
- talking with general contractor a range will be installed in kitcken and need to be added to mechanical permit by final.
- gas line to range which was existing will remain and be used. General said plumbing contractor extended gas line for furnace and water heater and will reconnect range gas line.
- plumbing contractor has water lines running within 1" of common b vent talked with general about issue and he will contact plumber. Lines just need supported up to acheive clearances
Rough-in1/3/20201/3/20201/3/2020AFAIL
DetailsJack Reynolds
- need to add exhaust fan/ dryer vent to permit
- exhaust fan venting needs connected to fan when installed
- gas line to range is still disconnected. Need information on what the plan is for the gas line.
Final12/31/20191/3/20201/3/2020AFAIL
DetailsJack Reynolds
Please call Chris on your way 1-###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks

- This inspection should have been a R/I
Final12/31/20191/2/202012/31/2019ACANC
DetailsJack Reynolds
We have vented the bath and dryer. The plumber did the gas piping and will be tying in the range. Builder ###-####. HVAC ###-####. Phone #: ###-#### >> Inspection requested via web by Arielle Hendricks Inspection cancelled from web by: Arielle Hendricks
Final12/30/201912/30/201912/30/2019PPEND
DetailsEric Strole
Owner: Chris ###-####
HVAC: ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks-Need to figure out who is going to install dryer exhaust, bath fan exhaust & hook up disconnected gas line to kitchen stove.
Rough-in12/26/201912/27/201912/27/2019PNR
DetailsBen Livingston
Jeremy ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- still working on repairs -
Final12/23/201912/24/201912/24/2019PFAIL
DetailsChad Schwendiman
Please inspect early PM and call Jeremy on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - Not allowed to use building cavities as ducts or plenums. Need to run a duct in the joist space for returns in bedrooms. This should be scheduled as a rough in inspection because we will need to verify combustion air opening in mechanical room for a final.