Final | 3/23/2020 | 3/24/2020 | 3/24/2020 | P | PASS |
Brian Scoles
|
|
|
CORRECTIONS MADE PLEASE RE-INSPECT GARAGE CODE 0425, OR 3484 Phone #: ###-#### Inspection requested via web by Oleg Chervak- final ok
|
Final | 3/20/2020 | 3/23/2020 | 3/23/2020 | P | FAIL |
Brian Scoles
|
|
|
garage code 3484 or 0425 Phone #: ###-#### Inspection requested via web by Oleg Chervak- need to seal gas line penetration exterior at meter location- need to tape insulation to filter box on sides exposed insulation showing
|
Rough-in | 1/22/2020 | 1/22/2020 | 1/22/2020 | P | PASS |
Brian Scoles
|
|
|
THE MAN-J HAD AN ERR, WE CORRECTED IT, IT NOW SHOWS 10X20 DUCT AND 16 SUPPLY IN ATTIC. SENT IN FOR APPROVAL, ROUGH COPY WILL BE LEFT ON SITE FOR YOU, PLEASE RE-INSPECT, WILL HAVE APPROVED COPY ON FINAL Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I HVAC and fireplace ok- have resubmitted man j onsite at final
|
Rough-in | 1/20/2020 | 1/21/2020 | 1/21/2020 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak 1- supply main in attic needs to be 18" round not 16" round as ran per man j 2- need to secure w/h b vent in chase 2nd floor
left do not cover sticker
|
Pressure Test | 1/17/2020 | 1/21/2020 | 1/21/2020 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass tagged meter location- 5lb flue pass
|
Rough-in | 1/17/2020 | 1/21/2020 | 1/20/2020 | A | CANC |
Brian Scoles
|
|
|
MEC AND FIREPL Phone #: ###-#### >> Inspection requested via web by Oleg Chervak Inspection cancelled from web by: Oleg Chervak
|